PCE Instruments PCE-TDS 200+ S-SW-KIT BTU Meter with 32 GB Data Memory
- Part #:PCE-TDS 200+ S-SW-KIT
- Condition:Brand New







BTU Meter / Clamp on Heat meter with 32 GB data memory / measuring range ±32 m/s / reproducibility ±0.5 % of measured value / different measuring probes / alarm limit values / 2.8 " LC display / for all media
The BTU Meter / Clamp on Heat meter has a measuring range of ±32 m/s. With an accuracy of ±1.5 % f.s. for a pipe diameter of DN ≥50, ±3.5 % f.s. for a pipe diameter of DN <50 and a reproducibility of ±0.5 % f.s., the ultrasonic flow meter is a particularly precise measuring device. An installation aid is available for installing the sensors of the ultrasonic flow meter. The installation aid graphically displays the signal quality of the ultrasonic flow meter. In addition, it is graphically displayed whether the sensors of the ultrasonic flow meter are positioned at the correct distance from each other. To carry out flow measurements with the ultrasonic flow meter, the flow velocity, the volume flow and the volume are displayed after entering the pipe and medium specifications. The ultrasonic flow meter displays the measured values in a wide range of units. For example: m³, l, gal, igl, mgl, cf, bal, ib and ob.
During a measurement, it is possible to record the measured values via the data logger function of the ultrasonic flow meter. Start and stop conditions and the storage interval can be set from 1 second to 12 hours for the ultrasonic flow meter. A memory point of the ultrasonic flow meter contains all measured values once. The measured values are stored on the 32 GB built-in memory of the ultrasonic flow meter. 10 million measuring points can be stored on the ultrasonic flow meter.
In order to determine the amount of heat with the ultrasonic flow meter, two additional thermocouples are required. These are available with the PCE-TDS 200+. The two thermocouples of the ultrasonic flow meter are connected to the flow and return of a pipe system. Based on the temperature difference and the measured flow rate, the ultrasonic flow meter can determine the amount of heat. If required, the ultrasonic flow meter can calculate and display the costs per unit of heat simultaneously during the measurement. Thus, the ultrasonic flow meter is used, for example, in the inspection of heating systems.
The LC color display of the ultrasonic flow meter has a size of 2.8" and is therefore easy to read.
PCE-TDS 200 S SENSOR
Small sensor pair for pipe diameters DN 15 ... 100 / 20 ... 108 mm. Suitable for particularly small pipes. The sensors have a particularly small dimension of 45 x 30 x 30 mm and a temperature resistance of -30 ... 160 °C. Thanks to the magnets on the underside, the sensors can be mounted on ferrous metals. In addition, the sensors for the ultrasonic flow meter can be connected to the pipe by means of detachable cable ties.
Features:
- Measuring range ±32 m/s
- USB-C interface for data transfer
- Reproducibility ±0.5 % of measured value
- Heat quantity measurement
- Data memory for 10 million measuring points
- individually adjustable alarm limits
Includes:
- 1 x Ultrasonic flow meter PCE-TDS 200+ S-KIT
- 2 x Temperature sensor TF-RA330
- 1 x Flow sensor PCE-TDS 200 S SENSOR (pair)
- 2 x 5 m connection cable
- 2 x detachable cable ties
- 1 x power supply unit
- 1 x USB-C cable
- 1 x ultrasonic contact gel
- 1 x PCE measuring tape
- 1 x plastic case
- 1 x Software
- 1 x instruction manual
- You May Also Like
- Your Recently Viewed
- Reviews
- Q&A
| Flow measurement | |
| Measuring range | ±32 m/s |
| Accuracy | 0,001 m/s |
| DN ≥50 mm: ±1.5 % rdg. for velocities > 0.3 m/s | |
| DN <50 mm: ±3.5 % rdg. for velocities > 0.3 m/s | |
| Reproducibility | ±0.5 % of measured value |
| PCE-TDS 200 S SENSOR | Sensor pair |
| Pipe diameter | DN 15 ... 100 / 20 ... 108 mm |
| Temperature resistance | -30 ... 160 °C |
| Dimension | 45 x 30 x 30 mm |
| Measuring method | Z, V, N, W |
| Medium | - water |
| - sea water | |
| - oil | |
| - crude oil | |
| - methanol | |
| - ethanol | |
| - diesel | |
| - petrol | |
| - petroleum | |
| - user defined | |
| (manual input of the sound velocity from the medium) | |
| All liquids with an impurity | <5 % |
| Pipe material | - copper CU |
| - steel FE | |
| - stainless steel VA | |
| - aluminium AL | |
| - brass ME | |
| - cast iron CI | |
| - iron FE | |
| - nickel NI | |
| - titanium TI | |
| - zink ZI | |
| - acrylic AC | |
| - polyethylene PE | |
| - polypropylene PP | |
| - polyvinyl chloride PVC | |
| - nylon NY | |
| - user defined | |
| (manual input of the transversal sound velocity | |
| of the pipe material) | |
| Inner pipe lining | - no lining |
| - user defined | |
| - epoxy resin | |
| - rubber | |
| - mortar | |
| - polystyrene PS | |
| - polyethylene PE | |
| - polytetrafluoroethylene PTFE | |
| - polyurethane PU | |
| - polypropylene PP | |
| - user defined | |
| (manual input of the longitudinal sound velocity | |
| of the inner lining of the pipe) | |
| Measurement parameters | flow velocity, volume flow and volume |
| Units (dimensions) | mm, in |
| Units (flow velocity) | m/s, ft/s |
| Units (volume flow) | m³, l, gal, igl, mgl, cf, bal, ib, ob |
| Time specification | seconds, minutes, hours, days |
| Units (volume) | m³, l, gal, igl, mgl, cf, bal, ib, ob |
| Temperature measurement | |
| Measuring range | Accuracy |
| Type B: 600 ... 1800 °C | Type B: ±(0.5 % + 3 °C) |
| Type E: -100 ... +900 °C | Type E: ±(0.4 % + 1 °C) |
| Type J: -100 ... 1150 °C | Type J: ±(0.4 % + 1 °C) |
| Type K: -100 ... +1370 °C | Type K: ±(0.4 % + 1 °C) |
| Type N: -100 ... + 1150 °C | Type N: ±(0.4 % + 1 °C) |
| Type R: 0 ... 1700 °C | Type R: ±(0.5 % + 3 °C) |
| Type S: 0 ... 1500 °C | Type S: ±(0.5 % + 3 °C) |
| Type T: -100 ... +400 °C | Type T: ±(0.4 % + 1 °C) |
| Resolution | 0.1 °C |
| Connectable thermocouples | B, E ,J ,K ,N ,R ,S ,T |
| Measuring parameters | flow rate, volume flow, volume, temperature, |
| Heat output and heat quantity | |
| Units (temperature) | °C / °F |
| Units (heat quantity) | K, kJ, MJ, Wh, kWh, MWh, Btu, kBtu, MBtu |
| Units (heat output) | W, kW, MW, J/h, kJ/h MJ/h, Btu/h, kBtu/h, MBtu/h |
| Cost display | EUR, Pound, USD, Turkish Lira, Zloty, Yen |
| Further specifications | |
| 2.8" LCD | 2,8" LCD |
| Menu | metrisch / imperial |
| Menu languages | German, English, French, Spanish, |
| Italian, Dutch, Portuguese, Danish, Turkish, Polish, German | |
| Turkish, Polish, Russian, Chinese, Japanese | |
| Operating and storage conditions | Temperature: -20 ... +65 °C |
| Humidity: 10 ... 95 % r. h., non-condensing | |
| Data logger | 32 GB memory capacity / 10 million measuring points |
| Unterface | USB (for online measurement, readout of the internal memory |
| memory and for recharging the battery) | |
| Protection class | IP52 |
| Power supply Internal | Internal: LiPo battery (3.7 V, 2500 mAh) |
| External: USB 5 VDC, 500 mA | |
| Operating time | approx. 10 h |
| Dimensions | 165 x 85 x 32 mm |
| Weight | 255 g |
Leave a review of this product!