Weber Sensors 3202.03 Vent-Captor Air Flow Switch 0.5–30 m/s PNP Output 24 VDC
- Part #:3202.03
- Model #:Vent-Captor
- Condition:Brand New

Key Facts
- Air flow switch designed for monitoring and controlling air velocity in ducts and systems
- Switching range from 0.5 to 30 m/sec for flexible airflow detection
- Normally open (NO) PNP transistor output for reliable signal switching
- Operates on 24 VDC for compatibility with industrial control systems
- Supplied with 2-meter ÖLFLEX cable for convenient installation
Overview
The Weber Sensors 3202.03 Vent-Captor Air Flow Switch is a reliable solution for monitoring airflow in ventilation ducts, HVAC systems, and industrial air handling applications. Designed to detect air velocity within a switching range of 0.5 to 30 m/sec, this sensor helps ensure proper system performance, safety, and operational efficiency.
With a normally open PNP transistor output, the Vent-Captor provides a dependable switching signal when airflow conditions meet the configured threshold. Its 24 VDC operation makes it suitable for integration into standard industrial control environments. The included 2-meter ÖLFLEX cable simplifies installation and connection in a variety of setups.
Product images are for reference only and may vary.
Features
- Wide airflow detection range for versatile HVAC and industrial applications
- PNP transistor output for easy integration with control systems
- Normally open switching configuration for standard signal logic
- 24 VDC operation compatible with common industrial power supplies
- Pre-wired with 2-meter ÖLFLEX cable for quick installation
Technical Specifications
- Product Type: Air flow switch
- Model: Vent-Captor 3202.03
- Switching Range: 0.5 to 30 m/sec (approx. 1.64 to 98.4 ft/sec)
- Output Type: PNP transistor, normally open (NO)
- Supply Voltage: 24 VDC
- Cable Length: 2 m (approx. 6.56 ft)
Use Cases
- Monitoring airflow in HVAC ducts and ventilation systems
- Ensuring proper air movement in industrial processes
- Protecting equipment by detecting insufficient airflow conditions
- Triggering alarms or system responses based on airflow thresholds
What’s Included
- 1 x Weber Sensors 3202.03 Vent-Captor Air Flow Switch
- Integrated 2-meter ÖLFLEX connection cable
Installation Notes
- Install in airflow direction as specified by the manufacturer
- Ensure proper positioning within ducts for accurate airflow detection
- Verify compatibility with control system input requirements (PNP signal)
Category FAQs
What does an air flow switch do?
An air flow switch monitors air velocity and triggers a signal when airflow reaches or falls below a set threshold.
What is a PNP transistor output?
A PNP output provides a positive switching signal, commonly used in industrial control systems for sensor integration.
What does normally open (NO) mean?
Normally open means the circuit remains open until the airflow condition is met, at which point the switch closes and sends a signal.
Where are air flow switches commonly used?
They are used in HVAC systems, ventilation ducts, cleanrooms, and industrial air handling systems.
Can this sensor detect low airflow conditions?
Yes, with a minimum switching range starting at 0.5 m/sec, it is suitable for detecting relatively low airflow levels.
Is this compatible with standard industrial systems?
Yes, 24 VDC operation and PNP output are widely compatible with industrial PLCs and control systems.
Does the cable come pre-installed?
Yes, the unit includes a pre-attached 2-meter ÖLFLEX cable for convenient installation.
Can this be used for safety or alarm systems?
Yes, it can be used to trigger alerts or shut down systems if airflow conditions fall outside acceptable limits.
- Specification Sheet
- Manuals/Tutorials
- You May Also Like
- Your Recently Viewed
- Reviews
- Q&A
| Medium | gaseous |
| Sensor data | |
| Measuring range | 0.3 to 30 m/s |
| Hysteresis | approx. 0.2 m/s |
| Adjustment | continuously adjustable |
| Display output status | LED red / green |
| Repeatability | < 3 % |
| Medium temperature | -20 °C to +70 °C |
| Ambient temperature | -20 °C to +70 °C |
| Pressure | atmospheric |
| Temperature drift | < 0.3 % per Kelvin |
| Mechanical data | |
| Protection class | IP 64 |
| Material sensor probe | ceramic with overglaze |
| Material housing | Ultradur (PBTP) |
| Mounting accessories | flange |
| Electrical connection | 2 m moulded oilflex cable / 3 x 0.5 mm2 |
| Electrical data | |
| Operating voltage | 24 VDC (16.8 - 31.2 VDC) |
| Switching current | max. 400 mA |
| Power consumption | 40 - 140 mA (max. flow) |
| Protection circuit | reverse polarity, short circuits and overload protection (ready for operation after correcting the short circuit) |
| Electrical output without flow | Normally Open PNP |