PCE Instruments PCE-ITE 50 Electrical Earth Tester, Up to 1000V Terminal Voltage

  • Part #:PCE-ITE 50
  • Condition:Brand New
0 Reviews Write a Review
  • List Price: $1,392.00
    • $1,266.70 / Each
      You Save: 9.0%
  • Free Shipping logoFree Shipping
See product details
Technical details

Isolation test

Terminal voltageMeasuring rangeResolutionAccuracyLoad currentShort circuit current

125V (0 ... 10 %)

0,125 ... 4 MΩ0.001 MΩ± (2% + 10 digits)1-mA at Last 125 kΩ<= 1-mA
4,001 ... 40 MΩ 0.01 MΩ± (2% + 10 digits)
40,01 ... 400 MΩ0.1 MΩ± (4% + 5 digits)
400,1 ... 1000 MΩ1 MΩ± (5% + 5 digits)

250V (0 ... 10 %)

0,125 ... 4 MΩ0.001 MΩ± (2% + 10 digits)1-mA at Last 250 kΩ<= 1-mA
4,001 ... 40 MΩ 0.01 MΩ± (2% + 10 digits)
40,01 ... 400 MΩ0.1 MΩ± (3% + 2 digits)
400,1 ... 1000 MΩ1 MΩ± (3% + 2 digits)

500V (0 ... 10 %)

0,125 ... 4 MΩ0.001 MΩ± (2% + 10 digits)1-mA at Last 500 kΩ<= 1-mA
4,001 ... 40 MΩ 0.01 MΩ± (2% + 10 digits)
40,01 ... 400 MΩ0.1 MΩ± (3% + 2 digits)
400,1 ... 1000 MΩ1 MΩ± (4% + 5 digits)

1000 V (0 ... 10 %)

0,125 ... 4 MΩ0.001 MΩ± (3% + 10 digits)1-mA at Last 1 MΩ <= 1-mA
4,001 ... 40 MΩ 0.01 MΩ± (2% + 10 digits)
40,01 ... 400 MΩ0.1 MΩ± (3% + 2 digits)
400,1 ... 1000 MΩ1 MΩ± (4% + 5 digits)

Low Ohm 

Measuring rangeResolution

Accuracy

Max. open circuit voltageOverload protection
2,000 Ω0.001 Ω

± (1.5% + 30 digits)

5.8V250 Vrms
20,00 Ω0.01 Ω

± (1.5% + 3 digits)

5.8V250 Vrms
200,0 Ω0.1 Ω

± (1.5% + 3 digits)

5.8V250 Vrms
2000 Ω1 Ω

± (1.5% + 5 digits)

5.8V250 Vrms

Continuity tester

Measuring range

Resolution

Max. open circuit voltageOverload protectionShort circuit current
2000 Ω

0.01 Ω

5.8V250 Vrms>= 200-mA

Grinding resistance

L-PE (Hi-Amp): Load current 4.0 A

Measuring range

Resolution

Accuracy

0.23 ... 9.99 Ω

0.01 Ω

± (4% + 4 digits)

10.0 ... 99.9 Ω

0.1 Ω

± (4% + 4 digits)

100 ... 999 Ω

1 Ω

± (4% + 4 digits)

L-PE (without tripping): Load current 15-mA

Measuring range

Resolution

Accuracy

0.23 ... 9.99 Ω

0.01 Ω

± (5% + 6 digits)

10.0 ... 99.9 Ω

0.1 Ω

± (5% + 6 digits)

100 ... 999 Ω

1 Ω

± (5% + 6 digits)

L-N: Load current 4.0 A

Measuring range

Resolution

Accuracy

0.23 ... 9.99 Ω

0.01 Ω

± (4% + 4 digits)

10.0 ... 99.9 Ω

0.1 Ω

± (4% + 4 digits)

100 ... 999 Ω

1 Ω

± (4% + 4 digits)

RCD Test

RCD (In)

10-mA, 30-mA, 100-mA, 300-mA, 650-mA, 1 A

Factors

x 1/2, x1, x2, x5

Accuracy of the tripping time

± (1% + 1 ms)

Signal form of the test current

Sine (AC), pulse (DC)

Tripping characteristics

G and S

Release time

0° or 180°

Voltage range

194 ... 260V AC (50/60 Hz)

Accuracy of current measurement

± (5% + 2 digits)

RCD TypesType A, Type B

Voltage measurement

Measuring range

Resolution

Accuracy

80...500 V AC/DC

1 V

± (2 % + 2 digits)

Frequency measurement

Measuring range

Resolution

Accuracy

45...65 Hz

1 Hz

±2 Hz

Grounding measurement

Measuring range

Resolution

Accuracy

0.00...99.99 Ω

0.01 Ω

± (2% + 30 digits)

100.0...999.9 Ω

0.1 Ω

± (2% + 6 digits)

1000...2000 Ω

1 Ω

± (2% + 6 digits)

General specifications

Power supply

8 x 1.2 ... 1.5V AA batteries

Operating time

ca. 15 h

Measurement category

CAT III 600V

Protection class

IP 65

Display

3.5" TFT (320 x 240 Pixel)

Operating environment

0 ... 45°C 0 ... 95% rH, non condensing

Measurements

24.2 x 10.5 x 14.5 cm

Weight

1.56 kg / 3.4 lbs