4-20mA Pressure Sensor
Features:
- Measures pressure from 0 to 200 psi, or 0-1,000 psi
- Requires a 24VDC power supply
- Compatible with refrigerants
- Suitable for higher range pressure applications, such as steam boilers and the high side/discharge lines on HVAC equipment which can exceed 500PSI
The sensor can be programed to detect pressure levels from 0 to 200 PSI. An alarm from the pressure sensor can indicate a problem with a pump, a possible clogged influent line, loss of suction, a downstream clog or perhaps a burst pipe. Any of those failures can cause a pump motor to overheat and warp. A 24V DC power supply is required to power the sensor.
- Specification Sheet
- Manuals/Tutorials
- You May Also Like
- Your Recently Viewed
- Reviews
- Q&A
| Process Connection | 1/4-18 NPT |
| Measuring Range | 0 to 200 psi, 0 to 1,000 |
| Operating Voltage | 8.5 to 36 VDC |
| Output Function | 4-20mA Analog |
| Accuracy | <0.5% |
| Operating Temperature | -40°F to 194°F |
| Protection | IP 67 | IP 69K |
| Dimensions | 2.63 x .75" |
| Cable Length | 6.6' |
| Notes | Requires a 24VDC power supply |