Multimeters Sonel WMUSMPI507 MPI-507 Multi-function Meter

  • Part #:WMUSMPI507
  • Condition:Brand New
0 Reviews Write a Review
Multimeters Sonel WMUSMPI507 MPI-507 Multi-function Meter
Multimeters Sonel WMUSMPI507 MPI-507 Multi-function Meter
Multimeters Sonel WMUSMPI507 MPI-507 Multi-function Meter
Multimeters Sonel WMUSMPI507 MPI-507 Multi-function Meter
Multimeters Sonel WMUSMPI507 MPI-507 Multi-function Meter
Multimeters Sonel WMUSMPI507 MPI-507 Multi-function Meter
Multimeters Sonel WMUSMPI507 MPI-507 Multi-function Meter
Multimeters Sonel WMUSMPI507 MPI-507 Multi-function Meter
Multimeters Sonel WMUSMPI507 MPI-507 Multi-function Meter
Multimeters Sonel WMUSMPI507 MPI-507 Multi-function Meter
Multimeters Sonel WMUSMPI507 MPI-507 Multi-function Meter
Multimeters Sonel WMUSMPI507 MPI-507 Multi-function Meter
    • $1,680.84 / Each
  • Free Shipping logoFree Shipping
See product details
3-4 Weeks Factory Lead Time
Check Availability
Quantity:
Technical details
Measurement functionsMeasurement rangeDisplay rangeResolutionAccuracy
Fault loop impedance
Fault loop ZL-PE, ZL-N, ZL-L0.13 Ω ... 1999 Ω acc. to IEC 615570.00 Ω ... 1999 Ωfrom 0.01 Ω±(5% m.v. + 3 digits)
Fault loop ZL-PEin RCD modefrom 0.5 Ω ... 1999 Ω acc. to IEC 615570.00 Ω ... 1999 Ωfrom 0.01 Ωfrom ±(6% m.v. + 5 digits)
Measurements of RCD parameters
RCD tripping test and measurement of tripping time tAmeasuring current 0,5 IΔn, 1 IΔn, 2 IΔn, 5 IΔn
general and short-time delay RCD0 ms ... 300 ms0 ms ... 300 ms1 ms±(2% m.v. + 2 digits)
selective RCD0 ms ... 500 ms0 ms ... 500 ms1 ms±(2% m.v. + 2 digits)
Measurement of RCD tripping current IAmeasuring current 0,3 IΔn ... 2,0 IΔn
for sinusoidal residual current (AC type)3.0 mA ... 500 mA3.0 mA ... 500 mAfrom 0.1 mA±5% IΔn
for unidirectional residual current and unidirectional with the 6 mA DC bias (type A)3.5 mA ... 420 mA3.5 mA ... 420 mAfrom 0.1 mA±10% IΔn
Earth resistance
3-pole method0.68 Ω ... 1999 Ω acc. to IEC 61557-50.00 Ω ... 1999 Ωfrom 0.01 Ωfrom ±(3% m.v. + 5 digits)
Insulation resistance
Measuring voltage 100 V100 kΩ ... 99.9 MΩ acc. to IEC 61557-20 kΩ ... 99.9 MΩfrom 1 kΩ±(5% m.v. + 8 digits)
Measuring voltage 250 V250 kΩ ... 199.9 MΩ acc. to IEC 61557-20 kΩ ... 199.9 MΩfrom 1 kΩ±(5% m.v. + 8 digits)
Measuring voltage 500 V500 kΩ ... 599.9 MΩ acc. to IEC 61557-20 kΩ ... 599.9 MΩfrom 1 kΩ±(5% m.v. + 8 digits)
Resistance of protective conductors and equipotential bondings
Measurement of resistance of protective conductors and equipotential bondings with ±200 mA current0.12 Ω ... 400 Ω acc. to IEC 61557-40.00 Ω ... 400 Ωfrom 0.01 Ω±(2% m.v. + 3 digits)
Measurement of resistance with low current0.0 Ω ... 1999 Ω0.0 Ω ... 1999 Ωfrom 0.1 Ω±(2% m.v. + 3 digits)
Phase sequence indicationin the same direction (correct), opposite direction (incorrect), UL-Lvoltage: 100 V ... 440 V (45 Hz ... 65 Hz)
"m.v." - measured value