Sonel WMUSMIC10 MIC-10 Insulation Resistance Meter

  • Part #:WMUSMIC10
  • Condition:Brand New
0 Reviews Write a Review
    • $574.66 / Each
  • Free Shipping logoFree Shipping
See product details
Technical details
Insulation resistance measurementMeasuring range:
  • Vn=50 V:50 kΩ ... 250.0 MΩ
  • Vn=100 V:100 kΩ ... 500.0 MΩ
  • Vn=250 V:250 kΩ ... 2.000 GΩ
  • Vn=500 V:500 kΩ ... 5.000 GΩ
  • Vn=1000 V:1000 kΩ ... 10.00 GΩ
RangeResolutionAccuracy
0.0 ... 999.9 kΩ0.1 kΩ± (3% m.v. + 8 digits)
1.000 ... 9.999 MΩ0.001 MΩ± (3% m.v. + 8 digits)
10.00 ... 99.99 MΩ0.01 MΩ± (3% m.v. + 8 digits)
100.0 ... 250.0 MΩ (for Vn= 50 V)0.1 MΩ± (3% m.v. + 8 digits)
100.0 ... 500.0 MΩ (for Vn= 100 V)0.1 MΩ± (3% m.v. + 8 digits)
100.0 ... 999.9 MΩ (for Vn≥ 250 V)0.1 MΩ± (3% m.v. + 8 digits)
1.000 ... 2.000 GΩ (for Vn= 250 V)0.001 GΩ± (3% m.v. + 8 digits)
1.000 ... 5.000 GΩ (for Vn= 500 V)0.001 GΩ±(4% m.v. + 6 digits)
1.000 ... 9.999 GΩ (for Vn= 1000 V)0.001 GΩ±(4% m.v. + 6 digits)
10.00 GΩ (for Vn= 1000 V)0.01 GΩ±(4% m.v. + 6 digits)
"m.v." - measured valueLow-voltage measurement of continuity of circuit and resistanceMeasuring range according to EN 61557-4: 0.10 ... 1999 Ω
RangeResolutionAccuracy
0.00 ... 19.99 Ω0.01 Ω±(2% m.v. + 3 digits)
20.0 ... 199.9 Ω0.1 Ω±(2% m.v. + 3 digits)
200 ... 1999 Ω1 Ω±(4% m.v. + 3 digits)
DC and AC voltage measurement
RangeResolutionAccuracy
0 ... 299.9 V0.1 V±(2% m.v. + 6 digits)
300 ... 600 V1 V±(2% m.v. + 2 digits)
Capacitance measurement
RangeResolutionAccuracy
1 ... 999 nF1 nF±(5% m.v. + 10 digits)
1.00 ... 9.99 uF0.01 uF±(5% m.v. + 10 digits)
  • Capacitance measurement result displayed after measurement of RISO
  • For measurement voltages below 100 V and measured resistance of less than 10 MΩ, the error of capacitance measurement is unspecified
Low-current resistance measurement
RangeResolutionAccuracy
0.00 ... 199.9 Ω0.1 Ω±(3% m.v. + 3 digits)
200 ... 1999 Ω1 Ω±(3% m.v. + 3 digits)