Resistance Meters PCE Instruments PCE-ET 5000 Advanced Earth Resistance Tester, Test Voltage 20, 48V AC

  • Part #:PCE-ET 5000
  • Condition:Brand New
0 Reviews Write a Review
Resistance Meters PCE Instruments PCE-ET 5000 Advanced Earth Resistance Tester, Test Voltage 20, 48V AC
Resistance Meters PCE Instruments PCE-ET 5000 Advanced Earth Resistance Tester, Test Voltage 20, 48V AC
Resistance Meters PCE Instruments PCE-ET 5000 Advanced Earth Resistance Tester, Test Voltage 20, 48V AC
Resistance Meters PCE Instruments PCE-ET 5000 Advanced Earth Resistance Tester, Test Voltage 20, 48V AC
Resistance Meters PCE Instruments PCE-ET 5000 Advanced Earth Resistance Tester, Test Voltage 20, 48V AC
  • List Price: $3,795.00
    • $3,453.50 / Kit
      You Save: 9.0%
  • Free Shipping logoFree Shipping
See product details
Typically In Stock
Check Availability
Quantity:
Technical details
3-pole earth resistance 
Test voltage20, 48V AC
Test frequency94 Hz, 105 Hz, 111 Hz, 128 Hz, AFC
Short circuit current250-mA
Test time26 seconds
Probe resistance Rs<100 kΩ
Auxiliary earth resistance Rh<100 kΩ
Resolution0.001 Ω
Measuring range Re0.02 Ω ... 300 kΩ
Accuracy± (5% + 10 digits)
Ust< 24V
Fst16 ... 400 Hz
  
The accuracy is ensured in an environment of 0 ... 28°C / 32 ... 82°F, < 80% RH (non-condensing).  Response time < 15 seconds (Time required to reach the specified accuracy, after the start of the measurement with the average function switched off.)
  
4-pole grounding resistor 
Test voltage20, 48V AC
Test frequency94 Hz, 105 Hz, 111 Hz, 128 Hz, AFC
Short circuit current250-mA
Test time30 seconds
Probe resistance Rs< 100 kΩ
Auxiliary earth resistance Rh< 100 kΩ
Resolution0.001 Ω
Measuring range Re0.02 Ω ... 300 kΩ
Accuracy± (5% + 10 digits)
Ust< 24V
Fst16 ... 400 Hz
  
The accuracy is ensured in an environment of 0 ... 28°C / 32 ... 82°F, < 80% RH (non-condensing).  Response time < 25 seconds (Time required to reach the specified accuracy, after the start of the measurement with the average function switched off.)
  
3-pole earth resistance with current clamp
Test voltage20, 48V AC
Test frequency94 Hz, 105 Hz, 111 Hz, 128 Hz, AFC
Short circuit current250-mA
Test time26 seconds
Probe resistance Rs< 100 kΩ
Auxiliary earth resistance Rh< 100 kΩ
Resolution0.001 Ω
Measuring range Re0.02 Ω ... 20 kΩ
Accuracy± (5% + 10 digits)
Ust< 24V
Fst16 ... 400 Hz
  
The accuracy is ensured in an environment of 0 ... 28°C / 32 ... 82°F, < 80% RH (non-condensing).  Response time < 25 seconds (Time required to reach the specified accuracy, after the measurement has started with the average function switched off.) If the current on the current probe is too low, the measurement can be aborted.
  
4-pole earth resistance with current clamp
Test voltage20, 48V AC
Test frequency94 Hz, 105 Hz, 111 Hz, 128 Hz, AFC
Short circuit current250-mA
Test time26 seconds
Probe resistance Rs< 100 kΩ
Auxiliary earth resistance Rh< 100 kΩ
Resolution0.001 Ω
Measuring range Re0.02 Ω ... 20 kΩ
Accuracy± (5% + 10 digits)
Ust< 24V
Fst16 ... 400 Hz
  
The accuracy is ensured in an environment of 0 ... 28°C / 32 ... 82°F, < 80% RH (non-condensing).  Response time < 25 seconds (Time required to reach the specified accuracy, after the measurement has started with the average function switched off.) If the current on the current probe is too low, the measurement can be aborted.
  
Grounding resistor only with current clamps
Test voltage48V AC
Test frequency94 Hz, 105 Hz, 111 Hz, 128 Hz, AFC
Short circuit current250-mA
Test time26 seconds
Measuring range Re0.02 Ω ... 150 Ω
Resolution0.001 Ω
Accuracy± (5% + 10 digits)
Ust< 24V
Fst16 ... 400 Hz
  
The accuracy is ensured in an environment of 0 ... 28°C / 32 ... 82°F, < 80% RH (non-condensing).  Response time < 25 seconds (Time required to reach the specified accuracy, after the measurement has started with the average function switched off.) If the current on the current probe is too low, the measurement can be aborted.
  
Soil resistance (removal resistance)
Test voltage20, 48V AC
Test frequency94 Hz, 105 Hz, 111 Hz, 128 Hz, AFC
Short circuit current250-mA
Test time26 seconds
Resolution0.001 Ω * m
Measuring range Re0.02 Ω ... 1000 kΩ * m
Accuracy± (5% + 10 digits)
  
2-pole resistance measurement (AC) 
Test voltage20V AC
Test frequency94 Hz, 105 Hz, 111 Hz, 128 Hz, AFC
Short circuit current250-mA
Test time26 seconds
Measuring range Re0.02 Ω ... 300 kΩ
Resolution0.001 Ω
Accuracy± (5% + 10 digits)
Ust< 24V
Fst16 ... 400 Hz
  
2-pole resistance measurement (DC) 
Test voltage20V DC
Short circuit current250-mA
Test time26 seconds
Measuring range Re0.02 ... 3 kΩ
Resolution0.001 Ω
Accuracy± (5% + 10 digits)
Ust< 3V
Fst16 ... 400 Hz
  
4-pole resistance measurement (DC) 
Test voltage20V DC
Short circuit current250-mA
Test time26 seconds
Measuring range Re0.02 Ω ... 3 kΩ
Resolution0.001 Ω
Accuracy± (5% + 10 digits)
Ust< 3V
Fst16 ... 400 Hz
  
Line compensation 
Test voltage20, 48V AC
Test frequency94 Hz, 105 Hz, 111 Hz, 128 Hz, AFC
Short circuit current250-mA
Test time26 seconds
Resolution0.001 Ω
Measuring range Re0.02 Ω ... 30 Ω
Accuracy± (3% + 10 digits)
Ust< 24V
Fst16 ... 400 Hz
  
Interference voltage 
Measuring range± 50V DC
 1 ... 50V AC
Resolution0.1V
Accuracy± (5% + 5 digits)
  
Interference current 
Measuring range20-mA ... 2 A
Resolution1-mA
Accuracy± (5% + 5 digits)
  
Interference frequency 
Measuring range16 ... 400 Hz
Resolution1 Hz
Accuracy± (1% + 10 digits)
  
Other specifications 
Data storage100 readings
Operating conditions0 ... 40°C / 32 ... 104°F, < 80% RH (non-condensing)
Charge ambient conditions to the battery                                                                  10 ... 40°C / 50 ... 104°F, < 80% rh (non-condensing)
Storage conditions  -10 ... 50°C / 50 ... 122°F, < 90% rh (non-condensing)
Storage conditions for the battery-20 ... 30°C / -4 ... 86°F, < 80% rh (non-condensing)
Storage height< 12,000 m / 39,370 ft
Operating altitude< 2,000 m / 6,561 ft
Clamp diameter51 mm
DisplayBacklit LCD, 9,999 digits
Display measuring range exceeded> LIMIT
Display below measuring range-
Measuring frequency earthing resistance / leakage current1 Hz (If the average value function is activated: one value every four seconds)
Measuring frequency voltage measurement2 Hz
Measuring frequency interference voltage4 Hz
Measuring frequency interference frequency1 Hz
Measuring frequency interference current1 Hz
interfacesMeasuring connection: E, ES, S, H, pliers connection USB-B, charging connection
Power supply batteries6 x 1.5V D LR14 batteries
Power supply battery1 x 7.2V nickel-metal hydride battery pack
Power supply power supplyPrimary: 100 ... 240V, 50 ... 60 Hz
 Secondary: 12V, 3A
Max. Power consumption with power supply15V A
Max. Power consumption with battery or rechargeable battery6V A
Running time in battery modeAbout 5 hours
Running time in the batteryAbout 9 hours (without backlight)
Maximum input voltage 
Maximum input voltage relative to earth300V rms (CAT III)
Insulation thickness6880V AC: 15 seconds
Overvoltage protection250V AC between the connections
Dimensions260 x 125 x 280 mm / 10.2 x 4.9 x 11 in
WeightAbout 2.5 kg / 5.5 lbs
StandardizeSafety: EN61010-1: 2001, EN61010-031: 2002
 Pollution degree 2, CAT III 300V,
 EMC: EN61000-3-2: 2000, IEC61326-1: 1997 A